S7 400 PLC主站下从站I/O信息丢失(瞬间中断/瞬间恢复)

CPU诊断信息

Event 5 of 120:  Event ID 16# 38C4
Distributed I/Os: station return
Address of the affected DP slave: station number:    1
DP master system ID:      1
Log. base address of the DP slave: Input address: 16368
Log. base address of the DP master:  16383
Requested OB: Rack failure OB (OB86)
Priority class: 25
External error, Outgoing event
01:54:39:229 am  03/03/13

=======================================================================
Event 6 of 120:  Event ID 16# 39B1
I/O access error when updating the process image input table 
Access error occurred for consistent user data 
process image partition no.:  0
start address of the affected I/O area:    734, area length:   8 
Requested OB: Program execution error OB (OB85)
Priority class: 25
External error, Incoming event
01:54:39:215 am  03/03/13


Event 7 of 120:  Event ID 16# 39B2
I/O access error when transferring the process image to the output modules 
Access error occurred for consistent user data 
process image partition no.:  0
start address of the affected I/O area:    734, area length:   8 
Requested OB: Program execution error OB (OB85)
Priority class: 25
External error, Incoming event
01:54:39:215 am  03/03/13

最佳答案

主要原因应该是DP通讯中断引起。建议检查DP头接线、DP总线、DP终端电阻、DP总线屏蔽等通讯环节。
请参考:《DP从站通讯经常中断》
http://www.ad.siemens.com.cn/service/answer/solution.aspx?Q_ID=56018&cid=1029
《S7-400PLC的PROFIBUS-DP通讯问题》
http://www.ad.siemens.com.cn/service/answer/solution.aspx?Q_ID=51107&cid=1040

提问者对于答案的评价:
仍在解决中。。。。