cpu报警消息

plc停止运行,cpu消息如下:
 Event 3 of 10:  Event ID 16# 4301
 Mode transition from STOP to STARTUP 
 STOP due to: Power failure
 Startup information: 
 – Time for time stamp at the last backed up power on
 – Single processor operation
 Current/last startup type:
 – Automatic warm restart after backed up power on
 Permissibility of certain startup types: 
 – Manual warm restart permitted
 – Automatic warm restart permitted
 Last valid operation or setting of the automatic startup type at power on:
 – Automatic warm restart after backed up power on
 Previous operating mode: STOP (internal)
 Requested operating mode: STARTUP (warm restart)
 Incoming event
 05:21:08.492 PM  10/20/1995

 
 Event 4 of 10:  Event ID 16# 38C4
 Distributed I/Os: station return
 Address of the affected DP slave: station number:   25
 DP master system ID:      1
 Log. base address of the DP slave: Input address:  2046
 Log. base address of the DP master:  32767
 Requested OB: Rack failure OB (OB86)
 OB not found, or disabled, or cannot be started in the current operating mode
 External error, Outgoing event
 05:20:59.004 PM  10/20/1995

 
 Event 5 of 10:  Event ID 16# 5371
 Distributed I/Os: end of the synchronization with a DP master 
 Slot of the DP master:   2 
 Number of distributed stations:   1
 Incoming event
 05:20:57.522 PM  10/20/1995

 
 Event 6 of 10:  Event ID 16# 4300
 Power on backed up 
 Previous operating mode: No voltage
 Requested operating mode: STOP (own initialization)
 Incoming event
 05:20:54.038 PM  10/20/1995

 
 Event 7 of 10:  Event ID 16# 494E
 Power failure
 Previous operating mode: STOP (internal)
 Requested operating mode: No voltage
 External error, Incoming event
 05:20:41.034 PM  10/20/1995

 
 Event 8 of 10:  Event ID 16# 38C4
 Distributed I/Os: station return
 Address of the affected DP slave: station number:   25
 DP master system ID:      1
 Log. base address of the DP slave: Input address:  2046
 Log. base address of the DP master:   2047
 Requested OB: Rack failure OB (OB86)
 OB not found, or disabled, or cannot be started in the current operating mode
 External error, Outgoing event
 05:20:02.164 PM  10/20/1995

 
 Event 9 of 10:  Event ID 16# 456F
 STOP caused by rack failure (OB not loaded or not possible, or no FRB) 
 Breakpoint in user program: Cyclic program (OB1) 
 Priority class:    1
 FC number:      2
 Module address:    246
 Previous operating mode: RUN
 Requested operating mode: STOP (internal)
 Internal error, Incoming event
 05:20:00.718 PM  10/20/1995

 
 Event 10 of 10:  Event ID 16# 39C4
 Distributed I/Os: station failure
 Address of the affected DP slave: station number:   25
 DP master system ID:      1
 Log. base address of the DP slave: Input address:  2046
 Log. base address of the DP master:   2047
 Requested OB: Rack failure OB (OB86)
 Priority class: 26
 External error, Incoming event
 05:20:00.705 PM  10/20/1995
 不知问题出在那,那位高手解释一下万分感谢!

 
 

最佳答案

1。首先PLC的诊断提示是:25#DP slave机架站号(即DP地址号)有故障,但又缺少OB86块(机架故障组织块),从而导致CPU中断停机;
 2。诊断提示中还列出由OB1块调用执行的FC2用户程序功能块可能有程序执行错误,导致CPU中断停机;
   因此,我建议你按的如下两项方法处理:
 1。首先将OB8X系列诊断组织块(例如OB80、OB81、OB82、OB83、OB84、OB85、OB86、OB88和OB121、OB122)下载至PLC中,可有效避免CPU的异常停机;
 2。然后仔细检查由OB1块调用执行的FC2用户程序功能块,是否有编程逻辑错误(例如:访问了实际不存在的存储地址编号、指针或数组索引号不存在,或超限等原因)。

提问者对于答案的评价:
可能是机架问题。

原创文章,作者:ximenziask,如若转载,请注明出处:https://www.zhaoplc.com/plc351854.html

(0)
打赏 微信扫一扫 微信扫一扫 支付宝扫一扫 支付宝扫一扫
上一篇 2021年7月5日
下一篇 2021年7月5日

相关推荐

  • 电脑上的倒计时如何引出到仪表上?

    目前,通过上位机实现倒计时,非常简单,但由于现场操作范围太大了,操作人员不可能一直在上位机旁边,因此想找一款倒计时仪表,可以实现与PLC通讯的,最好是多路4~20MA信号的。求推荐…

    自动化系统综合 2017年5月31日
  • 电机电流功率计算跟电度表计算

    现场有一台200KW的3相电机,在线测电流为160A,这样电机1小时要耗多少电,怎样计算,功率因数取多少合适,这样计算跟电度表计算会相差多少? 最佳答案 实际功率的计算=实际电流*…

    自动化系统综合 2017年11月4日
  • FB58脉冲调节温度

    我用FB58调节温度控制,用脉冲控制固态继电器来驱动加热棒,为什么我设定100度的时候温度老是在150度上下跳动?按道理应该是在100度上下跳动才对,还有就是脉冲的周期应该设多大才…

    自动化系统综合 2017年12月7日
  • 干扰

    小弟安装调试一设备,只要电机一运转,现场接近开关就会有干扰,此接近开关所用24v电压由开关电源提供,开关电源220v进线的相线和电机变频器其中一相并接,电机不启动接近开关正常,一启…

    自动化系统综合 2017年8月15日
  • PLC300与PLC200通讯问题

    现场又2台PLC300,315dpCPU  2台IM153-1模块.2台PLC200模块,如图.现在又一台PLC200接到主站PLC上,wincc老闪掉,就是隔…

    2017年6月19日
  • 那位师傅有STEP7 5.4和WINCC6.2软件能给发一个?谢谢

    STEP7 5.4WINCC6.2带授权的 最佳答案 请查看下载中心:用于 STEP 7 V5.4 中文版的 SP5&n…

    自动化系统综合 2020年11月1日
  • s7-300程序无法上载程序

    s7-300PLC用西门子USB编程电缆,笔记本MPI方式无法上载程序,显示只能读出MPI站地址,CPU模块读不出型号,硬件组态有CPU版本号及固件号,更新也无法上载,真是郁闷,上…

    自动化系统综合 2017年8月18日
  • Win7系统的西门子软件兼容问题

    我打算给新笔记本安装W7系统,目前我新笔记本系统是W8 64位的,我想问下,该成W7系统的话,应该选W7 32位的还是W7 64位的系统?必须得安装W…

    自动化系统综合 2017年11月29日
  • 为什么屏蔽地与系统地不能相连接?

    屏蔽地要求单独一个接地体,它说与系统地相连会产生干扰,但是这个噪声干扰是什么啊?电压信号干扰吗?为什么会干扰啊?我连接了这个系统地的话接地电阻应该是越来越小的啊?干扰从何而来? 最…

    自动化系统综合 2020年11月1日
  • PLCSIM如何使用

    只知道是PLC仿真,却不知如何用,望告知,谢谢。 最佳答案 是dlhdf8767@sina.com这邮箱吗? 已发送,请查收! 提问者对于答案的评价:已收到,谢谢。

    自动化系统综合 2020年11月1日

发表回复

登录后才能评论