无法打开或启动WINCC

楼主以前用WINCC 7.1版本单独安装后打开项目没有问题,现在为了装PCS7把旧版本协助了,用PCS 7 8.1版本安装软件,安装的WINCC7.3创建新项目失败,因为项目管理器无法启动基本应用程序XREF。进PCS7 把WINCC组件卸载了重装还是那样。该怎么办呢???

问题补充:
SQL Server(WinCC)已经设置为自动并且启动了

图片说明:

无法打开或启动WINCC    无法打开或启动WINCC   

最佳答案

看看SQL Server(WinCC)是否启动了?
有使用远程桌面等远程软件吗?
参考下:
I have encountered this problem. If your problem happens locally and not on remote connection I think this can solve your problem.
I assume you have done something on the Microsoft SQL Server Surface Area Configuration tool called "SQL Server Surface Area Configuration". Go to this tool on the Start menu > Microsoft SQL Server 20XX > Configuration Tools > SQL Server Surface Area Configuration.
Then on the Services and Connections link. Check the "WinCC > Database Engine > Remote Connections" if it is using remote connections with TCP/IP and Named pipes. I just disabled the Remote connections and just changed to "Local connections only" since I still don”t need remote connections. Don”t forget to restart after making this change. I tried this without restarting and still received the error. But after restart it is completely gone.

This solved my problem. Please rate if this becomes helpful. I still haven”t got any rating haha.

提问者对于答案的评价:
谢谢,重装后解决的

原创文章,作者:ximenziask,如若转载,请注明出处:https://www.zhaoplc.com/plc364509.html

(0)
打赏 微信扫一扫 微信扫一扫 支付宝扫一扫 支付宝扫一扫
上一篇 2021年7月5日
下一篇 2021年7月5日

相关推荐

发表回复

登录后才能评论