Non-reversing motor starter Size 1 Three phase full voltage Solid-state overload relay OLRelay amp range 3-12A 380-440/440-480V 50/60HZ coil Combination type 10Amp circuit breaker Encl NEMA type 4X 304 S-steel Water/dust tight noncorrosive Extra-wide enclosure | |
product brand name | Class 18 & 26 | |
design of the product | Full-voltage non-reversing motor starter with motor circuit protector | |
special product feature | ESP200 overload relay | |
General technical data | ||
Height x Width x Depth [in] | 24 × 20 × 8 in | |
touch protection against electrical shock | NA for enclosed products | |
installation altitude [ft] at height above sea level maximum | 6560 ft | |
ambient temperature [°F] | ||
● during storage | -22 … +149 °F | |
● during operation | -4 … +104 °F | |
ambient temperature | ||
● during storage | -30 … +65 °C | |
● during operation | -20 … +40 °C | |
Horsepower ratings | ||
yielded mechanical performance [hp] for 3-phase AC motor | ||
● at 200/208 V rated value | 2 hp | |
● at 220/230 V rated value | 2 hp | |
● at 460/480 V rated value | 5 hp | |
● at 575/600 V rated value | 5 hp | |
Contactor | ||
size of contactor | NEMA controller size 1 | |
number of NO contacts for main contacts | 3 | |
operating voltage for main current circuit at AC at 60 Hz maximum | 600 V | |
operational current at AC at 600 V rated value | 27 A | |
mechanical service life (operating cycles) of the main contacts typical | 10000000 | |
Auxiliary contact | ||
number of NC contacts at contactor for auxiliary contacts | 0 | |
number of NO contacts at contactor for auxiliary contacts | 1 | |
number of total auxiliary contacts maximum | 8 | |
contact rating of auxiliary contacts of contactor according to UL | 10A@600VAC (A600), 5A@600VDC (P600) | |
Coil | ||
type of voltage of the control supply voltage | AC | |
control supply voltage | ||
● at AC at 50 Hz rated value | 380 … 440 V | |
● at AC at 60 Hz rated value | 440 … 480 V | |
holding power at AC minimum | 8.6 W | |
apparent pick-up power of magnet coil at AC | 218 VA | |
apparent holding power of magnet coil at AC | 25 VA | |
operating range factor control supply voltage rated value of magnet coil | 0.85 … 1.1 | |
percental drop-out voltage of magnet coil related to the input voltage | 50 % | |
ON-delay time | 19 … 29 ms | |
OFF-delay time | 10 … 24 ms | |
Overload relay | ||
reset function | Manual, automatic and remote | |
trip class | CLASS 5 / 10 / 20 (factory set) / 30 | |
adjustable current response value current of the current-dependent overload release | 3 … 12 A | |
make time with automatic start after power failure maximum | 3 s | |
relative repeat accuracy | 1 % | |
number of NC contacts of auxiliary contacts of overload relay | 1 | |
number of NO contacts of auxiliary contacts of overload relay | 1 | |
operational current of auxiliary contacts of overload relay | ||
● at AC at 600 V | 5 A | |
● at DC at 250 V | 1 A | |
contact rating of auxiliary contacts of overload relay according to UL | 5A@600VAC (B600), 1A@250VDC (R300) | |
insulation voltage (Ui) | ||
● with single-phase operation at AC rated value | 600 V | |
● with multi-phase operation at AC rated value | 300 V | |
Enclosure | ||
degree of protection NEMA rating | 4X, 304 stainless steel | |
design of the housing | dustproof, waterproof & resistant to corrosion | |
Circuit Breaker | ||
type of the motor protection | Motor circuit protector (magnetic trip only) | |
operational current of motor circuit breaker rated value | 10 A | |
adjustable current response value current of instantaneous short-circuit trip unit | 30 … 100 A | |
Mounting/wiring | ||
mounting position | Vertical | |
fastening method | Surface mounting and installation | |
type of electrical connection for supply voltage line-side | Box lug | |
type of connectable conductor cross-sections at line-side at AWG cables single or multi-stranded | 1x (14 AWG … 10 AWG) or 1x (12 AWG … 10 AWG) | |
temperature of the conductor for supply maximum permissible | 75 °C | |
material of the conductor for supply | AL or CU | |
type of electrical connection for load-side outgoing feeder | Screw-type terminals | |
tightening torque [lbf·in] for load-side outgoing feeder | 35 … 35 lbf·in | |
type of connectable conductor cross-sections at AWG cables for load-side outgoing feeder single or multi-stranded | 1x (14 … 2 AWG) | |
temperature of the conductor for load-side outgoing feeder maximum permissible | 75 °C | |
material of the conductor for load-side outgoing feeder | AL or CU | |
type of electrical connection of magnet coil | Screw-type terminals | |
tightening torque [lbf·in] at magnet coil | 5 … 12 lbf·in | |
type of connectable conductor cross-sections of magnet coil at AWG cables single or multi-stranded | 2x (16 … 12 AWG) | |
temperature of the conductor at magnet coil maximum permissible | 75 °C | |
material of the conductor at magnet coil | CU | |
type of electrical connection for auxiliary contacts | Screw-type terminals | |
tightening torque [lbf·in] at contactor for auxiliary contacts | 10 … 15 lbf·in | |
type of connectable conductor cross-sections at contactor at AWG cables for auxiliary contacts single or multi-stranded | 1x (12 AWG), 2x (16 … 14 AWG), 2x (18 … 16 AWG) | |
temperature of the conductor at contactor for auxiliary contacts maximum permissible | 75 °C | |
material of the conductor at contactor for auxiliary contacts | CU | |
type of electrical connection at overload relay for auxiliary contacts | Screw-type terminals | |
tightening torque [lbf·in] at overload relay for auxiliary contacts | 7 … 10 lbf·in | |
type of connectable conductor cross-sections at overload relay at AWG cables for auxiliary contacts single or multi-stranded | 2x (20 … 14 AWG) | |
temperature of the conductor at overload relay for auxiliary contacts maximum permissible | 75 °C | |
material of the conductor at overload relay for auxiliary contacts | CU | |
Short-circuit current rating | ||
design of the short-circuit trip | Instantaneous trip circuit breaker | |
maximum short-circuit current breaking capacity (Icu) | ||
● at 240 V | 100 kA | |
● at 480 V | 100 kA | |
● at 600 V | 25 kA | |
certificate of suitability | NEMA ICS 2; UL 508; CSA 22.2, No.14 | |
Further information | ||
Industrial Controls – Product Overview (Catalogs, Brochures,…)
www.usa.siemens.com/iccatalog
|
||
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/us/Catalog/product?mlfb=US2:18DUC82WH
|
||
Service&Support (Manuals, Certificates, Characteristics, FAQs,…)
https://support.industry.siemens.com/cs/US/en/ps/US2:18DUC82WH
|
||
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, …)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=US2:18DUC82WH&lang=en
|
||
Certificates/approvals
https://support.industry.siemens.com/cs/US/en/ps/US2:18DUC82WH/certificate
|
||
|
||
|
||
|
||
last modified: | 1/25/2022 | |
Date 5/20/2023 |
Subject to change without notice © Copyright Siemens 2023 |
原创文章,作者:[db:作者],如若转载,请注明出处:https://www.zhaoplc.com/plc829996.html